Parametric Analysis of a Mechanical Draft Cooling Tower using Two Mathematical Models
Cargando...
Archivos
Fecha
Autores
Obregon-Quiñones, Luis Guillermo
Título de la revista
ISSN de la revista
Título del volumen
Editor
Resumen
In the present work, a Matlab® computer code for cooling tower simulation was developed to perform a parametric analysis
that determines the effect of the column cross-sectional area on multiple operating variables such as air humidity, air and
water outlet temperature, among others. The computer code uses the Merkel's model and the CDAWC (Continuous
Differential Air-Water Contactor) model for later comparison. It was observed a decrease in the outlet water temperature
by approximately 14% when the tower's cross-sectional area increased from 1 to 2 m2. It increases the air outlet temperature
by about 17% due to increased air-water contact. A negative convective heat transfer in the air was obtained in the cooling
tower´s bottom due to the large amount of energy required for the heat transfer by vaporization, which was much larger
than the convective heat. The evaporative heat transfer is over 80% of the total heat transferred.